CDU Fieldnotes

Evidence detail

How to compare data center CDU capacity ratings

Keep each capacity beside the exact ATD, flow, and configuration stated by its source. Shared limits and method.

On a phone, scroll the table horizontally to see every field.

Reviewed claims and unresolved fields
Seller / productCapacity statementStated conditionRack basisOther reviewed detail
Eaton
Eaton ROL / RAL / RAA CDUs
ROL4000 2,000 kW @ 3°C ATD (500 GPM); ROL2300 1,150 kW @ 4°C / 2,300 kW @ 8°C ATD (400 GPM @ 55 psi); ROL1100 550 kW @ 4°C / 1,100 kW @ 8°C ATD (125 GPM @ 30 psi); RAL110 (4U L2L) 50 kW @ 6°C / 110 kW @ 12°C ATD (24 GPM @ 10 psi); RAA32 (10U L2A) 16 kW @ 12°C / 32 kW @ 24°C ATD (16 GPM @ 12 psi)
Eaton catalog integrates Boyd Thermal by Eaton; each model pairs a rated kW with its exact ATD and flow/pressure basis.
ROL4000: 2,000 kW @ 3°C ATD (500 GPM); ROL2300: 1,150 kW @ 4°C vs 2,300 kW @ 8°C ATD (400 GPM @ 55 psi); ROL1100: 550 kW @ 4°C vs 1,100 kW @ 8°C ATD (125 GPM @ 30 psi); RAL110: 50 kW @ 6°C vs 110 kW @ 12°C ATD (24 GPM @ 10 psi); RAA32: 16 kW @ 12°C vs 32 kW @ 24°C ATD (16 GPM @ 12 psi)
Same ROL2300 unit doubles rated kW from 4°C to 8°C ATD (400 GPM @ 55 psi); verify facility water temp and pressure drop.
Absent from selected factsSeal-less N+1 pumps, automatic leak shutoff, 3X pressure test; 0.2 µm side-stream filtration & 500 GPM on ROL4000-48U65 only (Vendor catalog claims; 0.2-micron side-stream filtration and 500 GPM apply specifically to ROL4000-48U65.)
Vertiv
Vertiv CoolChip CDU Family
70 kW (L2A In-Row); 121 kW (L2L In-Rack); 600–2,300 kW (L2L In-Row)
Nominal model capacities across L2A and L2L units; compare only at each model's stated ATD.
4°C ATD for L2L models (121–2300 kW); 11°C ATD for L2A model (70 kW)
Vendor table states ATD and L2A/L2L mode; facility supply water temperatures and pressure drop curves require datasheet/sales quote.
Absent from selected factsRedundant variable-speed pumps, 50/25 µm filtration, built-in leak detection (Vendor family specification; confirm model-specific pump redundancy and spare parts.)
CoolIT Systems
CoolIT CHx 2000
Cooling Capacity 2000 kW
Vendor states 2000 kW cooling capacity for CHx 2000; cross-check separately stated 5°C ATD and product sheet before comparison.
2000 kW cooling capacity at 5°C ATD
Vendor-stated capacity/approach-temperature pair; further facility-side conditions and test protocol not stated in this excerpt.
12 x GB300 NVL72 racks per CDU
Vendor-stated model-specific rack basis. Keep exact GB300 NVL72 configuration; do not generalize to all racks.
Price and redundancy absent from selected facts
Johnson Controls / Silent-Aire
Silent-Aire Configurable CDU (SACDU)
SACDU 1050 (1,050 kW) and SACDU 2300 (2,300 kW) L2L CDUs
Document dated September 30, 2026; shipping scheduled March 15, 2027.
4°C (7.2°F) ATD at 1.5 LPM/kW; water primary / PG25 secondary; N+1 pumps on 1 MW unit only
N+1 redundant pump option is available on the 1 MW (1050 kW) unit only; confirm delivery timeline (Mar 2027).
Absent from selected factsPrice and redundancy absent from selected facts
Motivair by Schneider Electric
Motivair In-Rack CDU
cooling capacity of up to 105kW with IT cooling systems
Vendor states up to 105 kW for this in-rack CDU with IT cooling systems; conditions and exact test basis not stated in this sentence.
No separate ATD row; Vendor states up to 105 kW for this in-rack CDU with IT cooling systems; conditions and exact test basis not stated in this sentence.Absent from selected factsDesigned with redundant circulating pumps and advanced resiliency features (Vendor-stated design feature; no independent reliability validation.); Price: Request a Quote
JetCool
JetCool SmartSense CDU
Up to 300 kW per rack (in-rack L2L); modular row scaling 600 kW–1.8 MW (2–6 CDUs)
In-rack L2L requires 42-inch+ (1070 mm) deep 19-inch or ORV3 rack; ATD/inlet temp conditions in datasheet require confirmation.
No separate ATD row; In-rack L2L requires 42-inch+ (1070 mm) deep 19-inch or ORV3 rack; ATD/inlet temp conditions in datasheet require confirmation.Absent from selected factsPrice and redundancy absent from selected facts

Do not read a larger kW headline as a better fit until ATD, facility water temperature, and flow rate match.

Questions the pages do not settle

LiquidStack and Rittal: more rating conditions

LiquidStack specifies mode-dependent redundancy; Rittal’s US page leaves ATD open. Neither is a tested site result.

LiquidStack · Capacity and ATD

LiquidStack CDU 2.X: up to 2.5 MW at 4°C ATD.

End-of-row or rack-adjacent use. A headline rating is not a site load guarantee; obtain the full operating curve. Source

LiquidStack · Hydraulic duty point

The sheet lists 3.5 bar / 50 psi available head at 3,750 lpm / 990 gpm.

Use the stated pair, not an isolated maximum flow; have the supplier confirm coolant and pressure-drop conditions. Source

LiquidStack · Facility inlet

The CDU 2.X page supports facility water inlet temperatures up to 45°C.

The page does not establish that maximum flow, capacity and inlet temperature occur together. Source

LiquidStack · Pump modes

Single-pump mode provides internal N+1; dual-pump mode uses unit-to-unit redundancy.

Ask which operating mode your quote uses and what capacity remains after a pump fails. Source

LiquidStack · Power and controls

Control options include differential pressure, flow or pump speed; power options include dual A/B feeds with or without ATS.

These are configuration choices, not features proven to be included in every quoted unit. Source

Rittal · Liquid-to-liquid models

Rittal's US page lists a 150 kW in-rack CDU and 1 MW in-row CDU.

The same page's 70 kW rear-door liquid-to-air system is a different architecture. ATD for the L2L capacities is not stated there. Source

Rittal · Service access

Rittal says in-row sensors, controller and pumps can be replaced while the system runs.

A vendor design claim, not a tested uptime result or a site-specific maintenance procedure. Source