CDU Fieldnotes

Glossary

Data center liquid cooling terms: CDU, ATD and rack basis

These notes explain how the reviewed product pages use key terms. Where those pages omit a condition, that limit stays visible.

Coolant distribution unit (CDU)
Heat-exchange unit serving high-density liquid-cooled IT racks. Liquid-to-liquid (L2L) CDUs transfer heat from the secondary IT coolant loop into primary facility water; liquid-to-air (L2A) models reject heat to room air instead of facility water (for example, Vertiv lists both 70 kW (L2A In-Row); 121 kW (L2L In-Rack); 600–2,300 kW (L2L In-Row)). Exact wetted-loop measurement endpoints remain unknown unless given in a datasheet. See all models in the rating matrix.
Approach temperature difference (ATD)
Approach temperature difference (ATD) is the temperature gap between the primary cooling medium (facility supply water in L2L units, or ambient air in L2A units) and the secondary IT coolant supply. Wider ATD raises nominal kW on the same hardware: for example, Eaton states “ROL4000: 2,000 kW @ 3°C ATD (500 GPM); ROL2300: 1,150 kW @ 4°C vs 2,300 kW @ 8°C ATD (400 GPM @ 55 psi); ROL1100: 550 kW @ 4°C vs 1,100 kW @ 8°C ATD (125 GPM @ 30 psi); RAL110: 50 kW @ 6°C vs 110 kW @ 12°C ATD (24 GPM @ 10 psi); RAA32: 16 kW @ 12°C vs 32 kW @ 24°C ATD (16 GPM @ 12 psi)” (Same ROL2300 unit doubles rated kW from 4°C to 8°C ATD (400 GPM @ 55 psi); verify facility water temp and pressure drop.), while Vertiv states “4°C ATD for L2L models (121–2300 kW); 11°C ATD for L2A model (70 kW)”. Compare all seller ATDs in the rating matrix.
Rack basis
The exact IT rack load and chassis configuration paired with a CDU capacity figure. For example, CoolIT Systems states “12 x GB300 NVL72 racks per CDU” (Vendor-stated model-specific rack basis. Keep exact GB300 NVL72 configuration; do not generalize to all racks.). See seller rack-basis notes.
Rating conditions
The operating boundaries—ATD, flow rate, pressure drop, primary/secondary fluids, and delivery status—required to interpret a kW rating. For example, CoolIT Systems states “2000 kW cooling capacity at 5°C ATD” (Vendor-stated capacity/approach-temperature pair; further facility-side conditions and test protocol not stated in this excerpt.). Other vendor conditions live in the rating condition matrix.