CDU Fieldnotes

Direct-to-chip liquid cooling · US scope

Compare data center CDU capacity with its rating conditions

Published CDU capacities shift sharply with approach temperature (ATD) and rating conditions. Compare eight reviewed seller groups in their native units. LiquidStack and Rittal details ↓

Reviewed vendor statements · 8 reviewed seller groups

CDU capacity and stated rating conditions

Full condition matrix →

Eaton

Eaton ROL / RAL / RAA CDUs

Stated capacity

ROL4000 2,000 kW @ 3°C ATD (500 GPM); ROL2300 1,150 kW @ 4°C / 2,300 kW @ 8°C ATD (400 GPM @ 55 psi); ROL1100 550 kW @ 4°C / 1,100 kW @ 8°C ATD (125 GPM @ 30 psi); RAL110 (4U L2L) 50 kW @ 6°C / 110 kW @ 12°C ATD (24 GPM @ 10 psi); RAA32 (10U L2A) 16 kW @ 12°C / 32 kW @ 24°C ATD (16 GPM @ 12 psi)

Stated ATD & rating basis

ROL4000: 2,000 kW @ 3°C ATD (500 GPM); ROL2300: 1,150 kW @ 4°C vs 2,300 kW @ 8°C ATD (400 GPM @ 55 psi); ROL1100: 550 kW @ 4°C vs 1,100 kW @ 8°C ATD (125 GPM @ 30 psi); RAL110: 50 kW @ 6°C vs 110 kW @ 12°C ATD (24 GPM @ 10 psi); RAA32: 16 kW @ 12°C vs 32 kW @ 24°C ATD (16 GPM @ 12 psi)

Controls/filtration: Seal-less N+1 pumps, automatic leak shutoff, 3X pressure test; 0.2 µm side-stream filtration & 500 GPM on ROL4000-48U65 only.

Same ROL2300 unit doubles rated kW from 4°C to 8°C ATD (400 GPM @ 55 psi); verify facility water temp and pressure drop. Eaton catalog integrates Boyd Thermal by Eaton; each model pairs a rated kW with its exact ATD and flow/pressure basis. Vendor catalog claims; 0.2-micron side-stream filtration and 500 GPM apply specifically to ROL4000-48U65.

View Eaton source ↗

Vertiv

Vertiv CoolChip CDU Family

Stated capacity

70 kW (L2A In-Row); 121 kW (L2L In-Rack); 600–2,300 kW (L2L In-Row)

Stated ATD & rating basis

4°C ATD for L2L models (121–2300 kW); 11°C ATD for L2A model (70 kW)

Controls/filtration: Redundant variable-speed pumps, 50/25 µm filtration, built-in leak detection.

Vendor table states ATD and L2A/L2L mode; facility supply water temperatures and pressure drop curves require datasheet/sales quote. Nominal model capacities across L2A and L2L units; compare only at each model's stated ATD. Vendor family specification; confirm model-specific pump redundancy and spare parts.

View Vertiv source ↗

CoolIT Systems

CoolIT CHx 2000

Stated capacity

Cooling Capacity 2000 kW

Stated ATD & rating basis

2000 kW cooling capacity at 5°C ATD

Rack basis: 12 x GB300 NVL72 racks per CDU.

Vendor-stated capacity/approach-temperature pair; further facility-side conditions and test protocol not stated in this excerpt. Vendor states 2000 kW cooling capacity for CHx 2000; cross-check separately stated 5°C ATD and product sheet before comparison. Vendor-stated model-specific rack basis. Keep exact GB300 NVL72 configuration; do not generalize to all racks.

View CoolIT Systems source ↗

Johnson Controls / Silent-Aire

Silent-Aire Configurable CDU (SACDU)

Stated capacity

SACDU 1050 (1,050 kW) and SACDU 2300 (2,300 kW) L2L CDUs

Stated ATD & rating basis

4°C (7.2°F) ATD at 1.5 LPM/kW; water primary / PG25 secondary; N+1 pumps on 1 MW unit only

Rack basis and pricing route absent from reviewed capture.

N+1 redundant pump option is available on the 1 MW (1050 kW) unit only; confirm delivery timeline (Mar 2027). Document dated September 30, 2026; shipping scheduled March 15, 2027.

View Johnson Controls / Silent-Aire source ↗

Motivair by Schneider Electric

Motivair In-Rack CDU

Stated capacity

cooling capacity of up to 105kW with IT cooling systems

Stated ATD & rating basis

No separate ATD row in reviewed capture

Controls/filtration: Designed with redundant circulating pumps and advanced resiliency features · Price route: Request a Quote.

Vendor states up to 105 kW for this in-rack CDU with IT cooling systems; conditions and exact test basis not stated in this sentence. Vendor-stated design feature; no independent reliability validation. Page exposes a request-a-quote route; no numeric public price was observed. This does not prove pricing is never published.

View Motivair by Schneider Electric source ↗

JetCool

JetCool SmartSense CDU

Stated capacity

Up to 300 kW per rack (in-rack L2L); modular row scaling 600 kW–1.8 MW (2–6 CDUs)

Stated ATD & rating basis

No separate ATD row in reviewed capture

Rack basis and pricing route absent from reviewed capture.

In-rack L2L requires 42-inch+ (1070 mm) deep 19-inch or ORV3 rack; ATD/inlet temp conditions in datasheet require confirmation.

View JetCool source ↗

Eight seller groups have reviewed specifications here. The original list separately named Schneider and Motivair, which this site groups together. Boyd’s standalone redirect, Mitsubishi Electric and Accelsius remain outside the admitted product records. See shared limits.


LiquidStack

CDU 2.X

LiquidStack CDU 2.X: up to 2.5 MW at 4°C ATD. Source

3.5 bar at 3,750 lpm; internal N+1 is single-pump mode. Unit-to-unit redundancy uses dual-pump mode. Full conditions

Rittal

CDU In-Rack / In-Row

Rittal's US page lists a 150 kW in-rack CDU and 1 MW in-row CDU. Source

ATD is not stated on the US page. The 70 kW liquid-to-air system is a different architecture. Full conditions

Before you compare

What to request from each supplier

  1. Which facility water supply and return temperatures apply?
  2. What flow and pressure-drop basis supports the capacity?
  3. What does the stated approach temperature difference (ATD) cover?
  4. Which exact rack basis and redundancy mode are included?

For commissioning, water chemistry, and facility-fit checks, use the buyer question list.


Go deeper