EAEaton
Eaton ROL / RAL / RAA CDUs
Stated capacity
ROL4000 2,000 kW @ 3°C ATD (500 GPM); ROL2300 1,150 kW @ 4°C / 2,300 kW @ 8°C ATD (400 GPM @ 55 psi); ROL1100 550 kW @ 4°C / 1,100 kW @ 8°C ATD (125 GPM @ 30 psi); RAL110 (4U L2L) 50 kW @ 6°C / 110 kW @ 12°C ATD (24 GPM @ 10 psi); RAA32 (10U L2A) 16 kW @ 12°C / 32 kW @ 24°C ATD (16 GPM @ 12 psi)
Stated ATD & rating basis
ROL4000: 2,000 kW @ 3°C ATD (500 GPM); ROL2300: 1,150 kW @ 4°C vs 2,300 kW @ 8°C ATD (400 GPM @ 55 psi); ROL1100: 550 kW @ 4°C vs 1,100 kW @ 8°C ATD (125 GPM @ 30 psi); RAL110: 50 kW @ 6°C vs 110 kW @ 12°C ATD (24 GPM @ 10 psi); RAA32: 16 kW @ 12°C vs 32 kW @ 24°C ATD (16 GPM @ 12 psi)
Controls/filtration: Seal-less N+1 pumps, automatic leak shutoff, 3X pressure test; 0.2 µm side-stream filtration & 500 GPM on ROL4000-48U65 only.
Same ROL2300 unit doubles rated kW from 4°C to 8°C ATD (400 GPM @ 55 psi); verify facility water temp and pressure drop. Eaton catalog integrates Boyd Thermal by Eaton; each model pairs a rated kW with its exact ATD and flow/pressure basis. Vendor catalog claims; 0.2-micron side-stream filtration and 500 GPM apply specifically to ROL4000-48U65.
View Eaton source ↗VEVertiv
Vertiv CoolChip CDU Family
Stated capacity
70 kW (L2A In-Row); 121 kW (L2L In-Rack); 600–2,300 kW (L2L In-Row)
Stated ATD & rating basis
4°C ATD for L2L models (121–2300 kW); 11°C ATD for L2A model (70 kW)
Controls/filtration: Redundant variable-speed pumps, 50/25 µm filtration, built-in leak detection.
Vendor table states ATD and L2A/L2L mode; facility supply water temperatures and pressure drop curves require datasheet/sales quote. Nominal model capacities across L2A and L2L units; compare only at each model's stated ATD. Vendor family specification; confirm model-specific pump redundancy and spare parts.
View Vertiv source ↗CSCoolIT Systems
CoolIT CHx 2000
Stated capacity
Cooling Capacity
2000 kW
Stated ATD & rating basis
2000 kW cooling capacity at 5°C ATD
Rack basis: 12 x GB300 NVL72 racks per CDU.
Vendor-stated capacity/approach-temperature pair; further facility-side conditions and test protocol not stated in this excerpt. Vendor states 2000 kW cooling capacity for CHx 2000; cross-check separately stated 5°C ATD and product sheet before comparison. Vendor-stated model-specific rack basis. Keep exact GB300 NVL72 configuration; do not generalize to all racks.
View CoolIT Systems source ↗JCJohnson Controls / Silent-Aire
Silent-Aire Configurable CDU (SACDU)
Stated capacity
SACDU 1050 (1,050 kW) and SACDU 2300 (2,300 kW) L2L CDUs
Stated ATD & rating basis
4°C (7.2°F) ATD at 1.5 LPM/kW; water primary / PG25 secondary; N+1 pumps on 1 MW unit only
Rack basis and pricing route absent from reviewed capture.
N+1 redundant pump option is available on the 1 MW (1050 kW) unit only; confirm delivery timeline (Mar 2027). Document dated September 30, 2026; shipping scheduled March 15, 2027.
View Johnson Controls / Silent-Aire source ↗MBMotivair by Schneider Electric
Motivair In-Rack CDU
Stated capacity
cooling capacity of up to 105kW with IT cooling systems
Stated ATD & rating basis
No separate ATD row in reviewed capture
Controls/filtration: Designed with redundant circulating pumps and advanced resiliency features · Price route: Request a Quote.
Vendor states up to 105 kW for this in-rack CDU with IT cooling systems; conditions and exact test basis not stated in this sentence. Vendor-stated design feature; no independent reliability validation. Page exposes a request-a-quote route; no numeric public price was observed. This does not prove pricing is never published.
View Motivair by Schneider Electric source ↗JEJetCool
JetCool SmartSense CDU
Stated capacity
Up to 300 kW per rack (in-rack L2L); modular row scaling 600 kW–1.8 MW (2–6 CDUs)
Stated ATD & rating basis
No separate ATD row in reviewed capture
Rack basis and pricing route absent from reviewed capture.
In-rack L2L requires 42-inch+ (1070 mm) deep 19-inch or ORV3 rack; ATD/inlet temp conditions in datasheet require confirmation.
View JetCool source ↗Eight seller groups have reviewed specifications here. The original list separately named Schneider and Motivair, which this site groups together. Boyd’s standalone redirect, Mitsubishi Electric and Accelsius remain outside the admitted product records. See shared limits.